Magnavox W-10CR Installationsanleitung Seite 53

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 322
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 52
Specifications 37
5.8.2 – Output Connector
This connector has 16 optically isolated outputs that can
be configured for current sinking or sourcing. The sink-
ing/sourcing selection is done on the digital I/O card us-
ing a jumper. The factory setting is sinking.
Note: The movement of both jumpers is required for
proper operation. If only one jumper is moved the
digital inputs and outputs modes will be different.
Outputs
Signal Name Description Electrical Specification
B01 to B16 OUT (B01-B16)
Sink Mode: Voltage rating 24 volts, On state 0 to +2 volts @ 50 ma,
Off state leakage 0.6 ma maximum @ +24v.
Source Mode: Voltage rating 24 volts, On state +20 to +24 volts @ 50 ma, Off state
leakage 0.6 ma maximum.
Where: B is the board number.
Header
Pins
Jumpers
J7 J7
Jumper Positions
for
Sourcing I/O
Jumper Positions
for
Sinking I/O
OUTPUTS
1,2,9,10
3,4,11,12
5,6,13,14
7,8,15,16
24V
24V
COM
COM
OUTPUTS
1,2,9,10
3,4,11,12
5,6,13,14
7,8,15,16
24V
24V
COM
COM
Sinking Mode Sourcing Mode
Signal
Common
Signal
Common
OUT
OUT
OUT
Relay
coil
OUT
OUT
OUT
Relay
coil
Load
Load